Inspection History Details
Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0623-01145
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2023 | BULD - Electrical Clearance | Re-inspection required | Panel not ready for electrical clearance, fire block penetration at top plate right side of garage, fire foam top plate in laundry, add more nails to bang plate for range vent, pex lines in first floor bathroom within 12” of can lights must be insulated, nail plates needed under dining window, electrical work in house not ready, support 4-gang box at top landing of stairs, add nails to h2.5 clip at closet/pantry to the right side of bedroom 2’s closet, fire foam top plate of bedroom 3’s closet. | |
11/27/2023 | BULD - Electrical Clearance | Passed |