Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Gas Pressure Test 

Permit Number - TC-MDP-0623-01135

Inspection Description - COT - RSPL - Gas Pressure Test 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
12/08/2023 COT - RSPL - Gas Pressure Test  Re-inspection required Electrical not per plans, pex lines within 12” of can lights must be insulated, gas not under test, complete wiring in kitchen and at service panel, missing clean out at kitchen pantry, dwv and showers/tubs not under test, support 4-gang boxes in second floor, complete wiring second floor room at front of house, support duct registers on 3 sides second floor, complete wiring in loft, complete wiring for receptacle in laundry room, complete wiring in master bedroom, electrical clearance not ready, electrical and plumbing not per plans.
12/29/2023 COT - RSPL - Gas Pressure Test  Passed