Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
10/24/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Missing truss calcs, 3 studs are required to hold up beam by stairs. Add one more stud, missing second CS16x6 straps at beam by kitchen, left trimmer stud for back porch too short. Install correct size trimmer stud to full bear load of header, add nails to mass clip at shear wall, shear wall anchor bolts must be installed with 3”x3” plate washers per plans, anchor bolts missing at shear walls and perimeter of house.
10/31/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 3 studs are required to hold up beam by stairs. Add one more stud, missing second CS16x6 straps at beam by kitchen, left trimmer stud for back porch too short. Install correct size trimmer stud to full bear load of header, shear wall anchor bolts must be installed with 3”x3” plate washers per plans.
11/02/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed