Inspection Status: Re-inspection required

Inspection History: ENGR Engineering Final

Date Description Inspector Results Comments
01/28/2026 ENGR Engineering Final Re-inspection required Building requires address numbers visible from road. Numbers identifying units required. Accessible route to units is required. Sidewalk panels in front of doors have cross-slope of 7% (2% is max allowed). Sewer pipe at NE corner required to but cut down and capped. Fence at driveway blocks visibility of pedestrians, fence permit required.
01/30/2026 ENGR Engineering Final Re-inspection required (with fee) Accessible route to units is required. Sidewalk panels in front of doors have cross-slope of 7% (2% is max allowed). Fence at driveway blocks visibility of pedestrians, fence permit required.
02/03/2026 ENGR Engineering Final Not Ready Fence is now on a separate permit. Accessible route is not complete.
02/06/2026 ENGR Engineering Final Passed Site is complete in compliance with approved plans.