Parcel: 141460640


Addresses:

9629 E HARKES DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0524-00648

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/10/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 9/10/24: 4x10 under stairs required
12/09/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 12-9-24, 2x10 ledger under stairs required. See detail S6.2 #14. Per inspection from 9-10, inspector indicated loose sheathing. A letter for sheathing is required stating sheathing nailing was corrected per approved plans prior to installation of lath. Letter to be submitted as an attachment to the city for review and approval is required before issuing c of o. A reinspection or an engineer letter indicating current ledger at under stairs is sufficient. Also, electrical schedule doesn't match with number of actual AWG wires in installed.Therefore, have Austin Electric Company submit another letter to the city together with an updated schematic of electrical for review and approval. Again, this too will require city approval prior to issuing a Cof O.
12/31/2024 COT - RSBU - Exterior Clips/Sheathing  Passed 12/31/24 corrections made