Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0524-00620
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | 7/26/24: Fire wall shot pins required 24" O.C, Anchor bolt spacing required at 48" O.C, shot pins at interior walls missing throughout, blocking required at firewall at exterior walls, A35 clips required at cross bracing, anchor bolts required 12" from sill plate edge. | |
08/13/2024 | COT - RSBU - Exterior Clips/Sheathing | Canceled | 8/13/24: canceled by contractor | |
08/15/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | Ok to stucco exterior walls. |