Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
12-12-24, add anchor bolts to marked area entryway column, east & west sides of garage and at primary suite.Missing 2 rsp4's at marked area-west side of home. Add nails to garage shear wall as a result of over penetrating nailing together with shot pins at marked locations. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED |
| 12/16/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
12/16/24 corrections were made. Continued the inspection to ensure nothing else was missed. PASS |