Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
10-17-24, missing anchor bolts at patio columns, shear wall fasteners at primary suite not per plan, interior bearing not per detail sd3-13. Stopped inspection-more items may be added. |
| 11/15/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
11-15-24, since patio columns were covered up, provide a letter indicating that anchor bolts were added or remove a section and reschedule so that we may verify correction. See note: for interior load bearing walls. States "do not splice top plate within 3 inches of truss -full length of bearing location( PAGE S-3.1). |
| 11/25/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|