Inspection Status: Partial Pass
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 09/09/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
9/9/24: Anchor bolt spacing greater then 48" o.c throughout, shot pins must be spaced no greater than 24" and no greater than 6" from edge of sill plate. Will check at intermediate inspection. |
| 10/25/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|