Inspection Status: Re-inspection required
Inspection History: COT - LCME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2025 |
COT - LCME - Mechanical Final |
|
Re-inspection required |
4/30/25: unit 15202 primary bathroom water closet clearance not met 15" min , 15101 water hammer arrestor listing shall not be painted, 15102 secure orange nm cable at HVAC closet and fire caulk penetration at chase. Rails required at west stair case. |
| 05/05/2025 |
COT - LCME - Mechanical Final |
|
Passed |
5-5-25, required corrections from inspection dated 4/30/25 were made and verified. plumbing, mechanical, electrical, outdoor lighting & building final for units 15104, 15106, 15204, 15206, 15208, 15207, 15108, 15107, 15205, 15203, 15105, 15103 and Rooftop inspected & approved. |