Inspection Status: Not Ready

Inspection History: BULD - Electrical Clearance

Permit Number - TC-MDP-0523-01019

Inspection Description - BULD - Electrical Clearance

Inspection Status - Not Ready

Date Description Inspector Results Comments
11/06/2023 BULD - Electrical Clearance Not Ready 11/6/23: not ready
11/14/2023 BULD - Electrical Clearance Re-inspection required 11/14/23: seal all penetrations through top plate throughout, ufer needs to be properly fastened, wire size in bedrooms (2,3&1) not per plan (12AWG required per plans), pex must be 12'' from can lights, gas piping in laundry room needs to be properly secured, kitchen hood vent not installed, block registers on 3 sides, exhaust fan in attic missing, wire not made up in master closet, refrigerant lines need to be brazed into air handler, all penetrations going through vapor barrier need to be sealed, 3" Clean out missing at master bathroom per plan, missing Ev charger per plans. Dryer box not installed.
11/21/2023 BULD - Electrical Clearance Canceled Cancelled per John.
11/28/2023 BULD - Electrical Clearance Re-inspection required (with fee) Properly install GEC to uffer, seal all penetrations through top plate throughout, wire size in bedrooms (2,3&1) not per plan (12AWG required per plans), secure gas line, stopped inspection. Walk house to check for code compliance before calling for inspection.
11/30/2023 BULD - Electrical Clearance Passed