Inspection History Details
Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0523-00999
Inspection Description - BULD - Electrical Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2023 | BULD - Electrical Clearance | Re-inspection required | Uffer installed incorrectly, garage lights not per plans according to E1. Incorrect wire sizes. Garage lights also connecting to hallway and den. Not per plans, seal penetration at vapor barrier right side of garage, pex lines within 12” of can lights must be insulated, water lines not connected/completed, DWV not under test, showers/tubs not under test, secure copper line in master bathroom shower, incorrect wire sizes for outside receptacles. Not per E1 plan. Stopped inspection. Check house for code compliance before calling for inspection. | |
12/01/2023 | BULD - Electrical Clearance | Passed |