Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Permit Number - TC-MDP-0523-00993

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/07/2024 COT - RSEL - Electrical Final  Re-inspection required Last breaker missing labeling at dead front, EV charger installation not complete, no water going to house, kitchen outlets must be gfci protected, cooking appliances shall have vertical clearance above cooking stop/range no less than 30” to combustible material. No less than 24” to non-combustible listed materials per G2447.5, refrigerator must run on its own circuit, countertop to right of range missing outlet per E3901.4. STOPPED INSPECTION. More items may be added.
03/14/2024 COT - RSEL - Electrical Final  Passed