Inspection History Details
Inspection Status: Passed
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0523-00993
Inspection Description - BULD - Electrical Clearance
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2024 | BULD - Electrical Clearance | Passed | ||
12/05/2023 | BULD - Electrical Clearance | Re-inspection required | ufer installed incorrectly, staples needed left and right side of garage, open chase right side of garage, complete low voltage wiring house entrance, exposed wires in can light above kitchen island, missing nail plates throughout, support 4-gang box, complete wiring in laundry room, plumbing and electrical not per plans. | |
12/11/2023 | BULD - Electrical Clearance | Re-inspection required | missing dead front |