Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
|
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
9/23/26: STHD-10 at east side shear wall shall be attached to exterior sheathing, SW9-Shot pins shall be installed 4" o.c., add RSP4 clips at marked locations, SW11's require 3"x 3" washers, add anchor bolts at marked areas-anchors must be installed in the middle third of sill plate, add shot pins at marked locations, add nails to loose roof panels at marked areas-unable to gable ends at great room. Thus, provide a ladder to access roof, missing bracing on truss A4, missing boundary fasteners at great room/bathroom/garage-see detail 302-sloped blocking, missing detail 303-SW9,add 12/16d nails top plate splice at master bedroom. |
| 09/25/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
9-25-26 all items have been corrected. OK to proceed. |