Permit: TC-MDP-0426-00229

Parcel: 141155530


Addresses:

9743 E PANOPEIA DR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
09/23/2026 COT - RSBU - Roof NailingĀ  Re-inspection required 9/23/26: STHD-10 at east side shear wall shall be attached to exterior sheathing, SW9-Shot pins shall be installed 4" o.c., add RSP4 clips at marked locations, SW11's require 3"x 3" washers, add anchor bolts at marked areas-anchors must be installed in the middle third of sill plate, add shot pins at marked locations, add nails to loose roof panels at marked areas-unable to gable ends at great room. Thus, provide a ladder to access roof, missing bracing on truss A4, missing boundary fasteners at great room/bathroom/garage-see detail 302-sloped blocking, missing detail 303-SW9,add 12/16d nails top plate splice at master bedroom.
09/25/2026 COT - RSBU - Roof NailingĀ  Passed 9-25-26 all items have been corrected. OK to proceed.