Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 08/17/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
8-17-26: add shot pins to marked locations, add anchor bolts to marked locations, add RSP4 at marked locations, add 12-16d nails at at each side of a top plate splice per SN3/Detail 7, add anchor bolts 23" o.c. With 3x3: washers plates at SW11-at primary bedroom. Missing blocking at gable end bracing per SD2/Detail 301 at great room/bedroom and garage, missing h25A at marked location of north garage wall, missing nails at windows 8"o.c. Throughout, add blocking at restroom 9" above rim of tubs and additional blocking between 33" to 36" aff-per inclusive home design notes, add nails to loose roof panel at marked location at primary bedroom. |
| 08/19/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
8-19-26 all items have been corrected. OK to continue. |