Permit: TC-MDP-0426-00227

Parcel: 141156020


Addresses:

9740 E PANOPEIA DR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
07/06/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 7/6/26: RSP.4 required 32" o.c, fasteners at shear walls penetrate more than 1/8", SW11 require 3x3 washer plates at 23" o.c, Masa clip required to have 9 nails at south west corner of house, trimmer to king studs shall be fastened with nails at 8" o.c, fasteners shall be no closer than 3/8" from edge of shear walls, RSP4 AT REAR OPENING, seat and strap required at back porch beam, masa clip must be 4" from edge of sill plate, fasteners at shearwall required 4 " at edge and 12" at field sw11. STOPPED INSPECTION EXTERIOR NORTH EAST NOT COMPLETE AT WALK AND INTERIOR WAS NOT WALKED.
07/08/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 07/08/2026
Corrections made, walked roof and added htt5 at interior shear hold down missing.