Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0425-00276
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 1. Glulam not per plan in Garage, too big. Provide engineer letter for supports. 2. Broken truss in garage southeast, truss CJO1 and J02. Provide engineer letter. 3. Broken truss 2nd floor just above stairs marked on the floor in blue ink. 4. Broken cripple stud under window. 5. A35s missing under stairs on each stringer. 6. Awaiting Truss layout. 7. 2nd floor shear walls nailing not per plan on corners. 4” o.c. per plan. 8. Ok to dry roof. |
|
| 10/14/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required (with fee) | 10/14/25 All items above from previous have not been accomplished, with the exception of item 7. Next inspection will require a fee. |
|
| 11/07/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 11.07.2025 Verify before drywall the engineer letter/fix of truss in second floor near stairs and garage truss. Beam corrected. |
|
| 11/14/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 11.14.2025 All corrections made and fixed along with engineering letter provided. |