Parcel: 141461100


Addresses:

9629 E FRIEDEL DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-0425-00276

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/26/2025 COT - RSBU - Roof Nailing  Re-inspection required 1. Glulam not per plan in Garage, too big. Provide engineer letter for supports.
2. Broken truss in garage southeast, truss CJO1 and J02. Provide engineer letter.
3. Broken truss 2nd floor just above stairs marked on the floor in blue ink.
4. Broken cripple stud under window.
5. A35s missing under stairs on each stringer.
6. Awaiting Truss layout.
7. 2nd floor shear walls nailing not per plan on corners. 4” o.c. per plan.
8. Ok to dry roof.
10/14/2025 COT - RSBU - Roof Nailing  Re-inspection required (with fee) 10/14/25
All items above from previous have not been accomplished, with the exception of item 7. Next inspection will require a re-inspection fee.
11/07/2025 COT - RSBU - Roof Nailing  Passed 11.07.2025
Approved per plan, verify before drywall the engineer letter/fix of truss in second floor near stairs and garage truss. Beam corrected.