Parcel: 141460680


Addresses:

9585 E HARKES DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0424-00521

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/18/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required Missing shear wall at garage entry. Loose shear walls on both east and west end in kitchen areas. Stud spacing call for 12" o.c north wall of kitchen. Provide anchor bolts at marked areas. Nail masa clip at garage. Nosing exceeded 1 1/4" at landing. Plans call for two cs16 straps at both north and south shear wall tie downs. Stopped inspection. Other items may occur. 11/18/2024