Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0424-00511

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/10/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required Missing 6x6 post at porch entry. Provide 2x4 cross blocks above shear wall 12" o.c. Add anchor bolts at marked locations. Add shot pins to interior walls bottom plates. 10/10/2024
10/14/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10/14/24: missing anchor bolt at shear wall garage. Missing 6x6 post at entry
10/16/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed