Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0424-00496
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 8/22/24: shear walls loose on second floor. Need blocking at landing for stairs installed. Clips missing nailing on south side of home | |
| 08/26/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 8/22/24: shear walls loose on second floor. Need blocking at landing for stairs installed. Clips missing nailing on south side of home 8/26/24: Blocking required at stairwell landing, H2.5 missing at joist to top plate second floor, blocking required between joist, LTP4 missing at cantilever 24"o.c, web stiffeners required throughout, 2X blocking required at shear wall below second floor base plate, second floor sheathing must be properly fastened. |
|
| 08/28/2024 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |