Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
Door to walk in closet to low and too narrow, will need 32" after drywall, missing anchor bolts through or too close to edge of sill plate, loose studs and plate at electrical panel, need to move attic access, tply at garage to attic falling off, staple t-lay at shear walls 3 inches oc. Stopped inspection more items may be added |
| 06/24/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
6/24/25 corrections made |