Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
The login landing page when selecting 'View' is still occurring and is still pending further investigation.
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 10/10/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
Receptacle in bedroom 3 exceeding 12´. Ground wires need to be secured to ground screws in metal boxes. Add nail plate and seal electrical conduit at kitchen hood. Add nail plates to electrical lines that are less than an 1 1/4". Add nail plate to pex line in hall bathroom. Thermostat needs to be no higher than 54". Mechanical work incomplete. 10/10/2024 |
| 10/11/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
10/11/24: All noted items have been corrected. Okay to proceed with insulation and drywall work. |