Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 10/10/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Re-inspection required |
Receptacle in bedroom 3 exceeding 12´. Ground wires need to be secured to ground screws in metal boxes. Add nail plate and seal electrical conduit at kitchen hood. Add nail plates to electrical lines that are less than an 1 1/4". Add nail plate to pex line in hall bathroom. Thermostat needs to be no higher than 54". Mechanical work incomplete. 10/10/2024 |
| 10/11/2024 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
|
Passed |
10/11/24: All noted items have been corrected. Okay to proceed with insulation and drywall work. |