Parcel: 141434580


Addresses:

6739 E VIA DE AYATE


Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Gas Pressure Test 

Permit Number - TC-MDP-0424-00396

Inspection Description - COT - RSPL - Gas Pressure Test 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/28/2024 COT - RSPL - Gas Pressure Test  Re-inspection required 10-28-24, seal vapor barrier at garage, properly ground exterior light fixture at garage, gas not under pressure, thermostat wiring near entry to kitchen measured at 58 inches ( max height shall be 54 inches from grade), stopped inspection-additional items requiring correction may be noted.
10/29/2024 COT - RSPL - Gas Pressure Test  Re-inspection required 10-29-24, seal penetrations at garage, seal all staples on vapor barrier throughout, properly attach strap in bedroom 2, missing fire foam at penetrations inside storage room. Gas must be pressurized to 15psi for minimum of 10 minutes.
10/31/2024 COT - RSPL - Gas Pressure Test  Passed 10-31-24, gas pressure test approved.