Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Gas Pressure Test
Permit Number - TC-MDP-0424-00396
Inspection Description - COT - RSPL - Gas Pressure Test
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2024 | COT - RSPL - Gas Pressure Test | Re-inspection required | 10-28-24, seal vapor barrier at garage, properly ground exterior light fixture at garage, gas not under pressure, thermostat wiring near entry to kitchen measured at 58 inches ( max height shall be 54 inches from grade), stopped inspection-additional items requiring correction may be noted. | |
10/29/2024 | COT - RSPL - Gas Pressure Test | Re-inspection required | 10-29-24, seal penetrations at garage, seal all staples on vapor barrier throughout, properly attach strap in bedroom 2, missing fire foam at penetrations inside storage room. Gas must be pressurized to 15psi for minimum of 10 minutes. | |
10/31/2024 | COT - RSPL - Gas Pressure Test | Passed | 10-31-24, gas pressure test approved. |