Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - TC-MDP-0424-00386

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/21/2024 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required 6/21/24: Anchor bolts missing throughout 12" from edge of sill plate, anchor bolt spacing at shear walls not per plan, A35 clips required at cross bracing at gable end, truss bracing missing per truss clacs.
06/24/2024 COT - RSBU - Exterior Clips/Sheathing  Passed Corrections were made. 6/24/2024