Parcel: 140443010


Addresses:

6037 E CAMPOLINA TR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-0424-00386

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/21/2024 COT - RSBU - Roof Nailing  Re-inspection required 6/21/24: Anchor bolts missing throughout 12" from edge of sill plate, anchor bolt spacing at shear walls not per plan, A35 clips required at cross bracing at gable end, truss bracing missing per truss clacs. Roofing not checked no ladder provided.
06/24/2024 COT - RSBU - Roof Nailing  Passed Corrections were made. 6/24/2024