Permit: TC-MDP-0424-00386

Parcel: 140443010


Addresses:

6037 E CAMPOLINA TR

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof NailingĀ 

Date Description Inspector Results Comments
06/21/2024 COT - RSBU - Roof NailingĀ  Re-inspection required 6/21/24: Anchor bolts missing throughout 12" from edge of sill plate, anchor bolt spacing at shear walls not per plan, A35 clips required at cross bracing at gable end, truss bracing missing per truss clacs. Roofing not checked no ladder provided.
06/24/2024 COT - RSBU - Roof NailingĀ  Passed Corrections were made. 6/24/2024