Inspection Status: Re-inspection required

Inspection History: BULD - Electrical Clearance

Permit Number - TC-MDP-0424-00375

Inspection Description - BULD - Electrical Clearance

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/30/2024 BULD - Electrical Clearance Re-inspection required Roof is not loaded, missing blocking for A/C registers throughout house, DWV is not under water test, and several places where studs are bored for electrical wiring need bang plates to protect wire from damage by drywall screws.
BULD - Electrical Clearance Passed TEP ECO