Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0423-00899

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/07/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 3/7/24: Anchor bolt spacing at shear wall 13 greater than 17" o.c, Anchor bolts at shear wall 11 or greater require 3"x3" plate washer (missing throughout), shear wall fastening schedule not per plan throughout, shear walls up stairs need to be fastened per schedule at bottom plate throughout.
03/12/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed