Inspection History Details
Inspection Status: Not Ready
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0423-00852
Inspection Description - BULD - Electrical Clearance
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2023 | BULD - Electrical Clearance | Not Ready | 11/6/23: not ready | |
11/14/2023 | BULD - Electrical Clearance | Re-inspection required | 11/14/23: seal all penetrations through top plate throughout,properly secure uffer ground, garage lights needs to be on a circuit with only garage and be 12AWG per plan (currently tied in with bedroom 3, wiring in laundry room not per plan calls for 12AWG, wiring for stove top not installed, wiring in bedroom 1 not per plan, proper secure wall at laundry room, refrigerant lines not brazed to air handler. Seal vapor barrier in attic front of house, EV charger missing per plan. | |
11/21/2023 | BULD - Electrical Clearance | Canceled | Cancelled per John. | |
11/28/2023 | BULD - Electrical Clearance | Re-inspection required (with fee) | Properly install GEC to uffer, seal all penetrations through top plate throughout, garage lights needs to be on a circuit with only garage and be 12AWG per plan (currently tied in with bedroom 3, proper secure wall at laundry room, install HTT hold down for shear wall. Walk house to check for code compliance before calling for inspection. | |
11/30/2023 | BULD - Electrical Clearance | Passed |