Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 8-5-26: missing fire foam throughout top plate penetrations, fire foam all penetrations from 1st floor to 2nd floor decking, missing bank plates at entryway-see marked areas, condensation line must be secured, add fha plate/boca plate to top plate at east wall 1st floor DWV, fire foam all horizontal penetrations at garage-all unconditioned to conditioned areas require fire foam, seal penetrations at east wall vapor barrier-see marked areas. Stopped inspection-additional items may be added &2nd floor not inspected. | |
| 08/07/2026 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | 08/07/2026 All items addressed, added foam and straps to exhaust duct and unbound supply duct in upstairs primary bedroom, walked rest of building. |