Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
| Date |
Description |
Inspector |
Results |
Comments |
| 06/12/2025 |
COT - RSBU - Preslab |
|
Re-inspection required |
6/12/25: MASA clip spacing not per plan, pocket form for pt pull end shall be flush with form to prevent any concrete in cavity, #5 rebar reinforcement requires 30" overlap, damaged sheathing at pt cable must be taped, stationary end of pt cable shall have no more than 12'' of exposed sheathing, |
| 06/16/2025 |
COT - RSBU - Preslab |
|
Passed |
6-16-25: preslab, excavation, reinforcement and setbacks verified per plans. Okay to pour concrete |