Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
Permit Number - TC-MDP-0325-00163
Inspection Description - COT - RSBU - Preslab
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2025 | COT - RSBU - Preslab | Re-inspection required | 6/12/25: MASA clip spacing not per plan, pocket form for pt pull end shall be flush with form to prevent any concrete in cavity, #5 rebar reinforcement requires 30" overlap, damaged sheathing at pt cable must be taped, stationary end of pt cable shall have no more than 12'' of exposed sheathing, | |
| 06/16/2025 | COT - RSBU - Preslab | Passed | 6-16-25: preslab, excavation, reinforcement and setbacks verified per plans. Okay to pour concrete |