Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Excavation/Rebar/Zoning
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2024 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Re-inspection required |
6/6/24: reinforcement requires 3" clearance from earth (making contact throughout), PT pocket former not properly installed at garage, exposed cable at PT over the maximum allowable throughout on both ends. Footings must be 12" in depth, |
| 06/07/2024 |
COT - RSBU - Excavation/Rebar/Zoning |
|
Passed |
Corrections were made. Okay for concrete placement. 6/7/2024 |