Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0324-00347
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2024 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | 8/30/24: Anchor bolt spacing at bearing walls not per plan, fasteners at shear wall not per schedule, fasteners must not penetrate more than 1/8", anchor bolts at shear wall not per schedule, 1 in 3 Masa clips is allowed with one leg down (fix required), roof sheathing must be properly fastened, clips at top plate at 2nd floor must be properly fastened. Anchor bolts missing 12" from edge throughout. | |
09/04/2024 | COT - RSBU - Exterior Clips/Sheathing | Passed | Corrections were made. 9/4/2024 |