Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Outdoor Lighting

Permit Number - TC-MDP-0324-00274

Inspection Description - COT - RSEL - Outdoor Lighting

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/27/2024 COT - RSEL - Outdoor Lighting Re-inspection required Missing sewer cover in driveway, no tag on water line for post tension slab, condensation line missing 90 degree angle on pipe, maximum breaker size for a/c unit is 40 amps; 50 amp breaker installed. Stopped inspection not ready for final.
12/06/2024 COT - RSEL - Outdoor Lighting Passed 12/6/24 corrections were made