Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Permit Number - TC-MDP-0324-00274

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/27/2024 COT - RSME - Mechanical Final  Re-inspection required Missing sewer cover in driveway, no tag on water line for post tension slab, condensation line missing 90 degree angle on pipe, maximum breaker size for a/c unit is 40 amps; 50 amp breaker installed. Stopped inspection not ready for final.
12/06/2024 COT - RSME - Mechanical Final  Passed 12/6/24 corrections were made