Parcel: 138102050


Addresses:

160 E DREXEL RD


Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Grounding/Bonding 

Permit Number - TC-MDP-0324-00269

Inspection Description - COT - RSEL - Grounding/Bonding 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
08/12/2024 COT - RSEL - Grounding/Bonding  Re-inspection required UFER not in place. Missing electrical conduit for island. 8/12/2024
08/13/2024 COT - RSEL - Grounding/Bonding  Partial Pass UFER not in place. Missing electrical conduit for island. 8/12/2024
8/13/24: corrections made ok to proceed. Partial for UFER
10/04/2024 COT - RSEL - Grounding/Bonding  Canceled 10/4/24: canceled per contractor
10/08/2024 COT - RSEL - Grounding/Bonding  Re-inspection required UFER not in place. Missing electrical conduit for island. 8/12/2024
8/13/24: corrections made ok to proceed. Partial for UFER
10/4/24: canceled per contractor
10/8/24: fire blocking required on west wall at garage, nail plates required at condensate drain at garage, all penetrations through top plate must be sealed, proper terminate dryer exhaust vent above trusses, dryer vent duct must be supported mid way running in wall, pex lines must be supported 32" on vertical runs, fire blocking required at soffit at kitchen, kitchen hood must terminate 6" below soffit and chase must be sealed, receptacle missing at kitchen island, seal sleeves at kitchen island, revision required for change in wire size in multiple locations, flex duct must be supported throughout, DWV not under test, shower/tub must be under test, shot pins required throughout at interior sill plates, pour back required at bath tub, leak at bathtub, drywall screws are not allowed to support fan fixtures (please use proper fasteners).