Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - TC-MDP-0323-00672
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2023 | COT - RSBU - Exterior Clips/Sheathing | Re-inspection required | 7/21/23: all shear wall 11 and greater require 3"x3" plates, shear wall at garage missing nailing to bottom plate, anchor bolt spacing at shear wall 11 is 23" on center. Missing anchor bolt at shear wall in master at bottom plate. | |
07/25/2023 | COT - RSBU - Exterior Clips/Sheathing | Passed |