Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 09/08/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
9-8-26 trimmer to king stud at window openings are required to be (2)16d nails 3"o.c. Throughout * missing nails at header on back porch* missing H2.5A clip at back porch Northwest corner* shot pins are required throughout first floor 6 inches from edge and 32 inches from then on, on non loadbearing walls. Marked some shot pins, but not all* over penetrated nails at garage shearwall no more then 1/8" penetration* add anchor boats to Mark locations* stopped inspection at this time second floor truss calcs and roof inspection not walked. More items may be noted. Reinspection is required please re-walk before calling inspection in. |
| 09/11/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Canceled |
9-11-26 canceled per super |
| 09/15/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
9/15/26: per detail 303-blocking 24" o.c. is missing at WIC at bedroom. SW9 shows blocking directly above closet. Partial pass on roof-missing truss calculations. Reschedule when trades are out of space. |
| 09/17/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
9-17-26 all corrections have been made. Trust calcs are accurate OK to proceed |