Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Date Description Inspector Results Comments
09/08/2026 COT - RSBU - Roof Nailing  Re-inspection required 9-8-26 trimmer to king stud at window openings are required to be (2)16d nails 3"o.c. Throughout * missing nails at header on back porch* missing H2.5A clip at back porch Northwest corner* shot pins are required throughout first floor 6 inches from edge and 32 inches from then on, on non loadbearing walls. Marked some shot pins, but not all* over penetrated nails at garage shearwall no more then 1/8" penetration* add anchor boats to Mark locations* stopped inspection at this time second floor truss calcs and roof inspection not walked. More items may be noted. Reinspection is required please re-walk before calling inspection in.
09/11/2026 COT - RSBU - Roof Nailing  Canceled 9-11-26 canceled per super
09/15/2026 COT - RSBU - Roof Nailing  Re-inspection required 9/15/26: per detail 303-blocking 24" o.c. is missing at WIC at bedroom. SW9 shows blocking directly above closet. Missing truss calculations. Reschedule when trades are out of space.
09/17/2026 COT - RSBU - Roof Nailing  Passed 9-17-26 all corrections have been made. Trust calcs are accurate OK to proceed