Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Interior Shear Bracing
| Date |
Description |
Inspector |
Results |
Comments |
| 09/14/2026 |
COT - RSBU - Interior Shear Bracing |
|
Re-inspection required |
9/14/26: Fasteners shall be no closer than 3/8" from edge of drywall (Throughout), fasteners shall penetrate no more than 1/8" into drywall (throughout), SW1 at BDRM 2 and Primary W.I.C (spacing must be 7" o.c), patch damaged drywall throughout, Drywall shall be spaced no more than 1/2" from floor to bottom plate, 1/8" max spacing at joints between drywall panels. |
| 09/15/2026 |
COT - RSBU - Interior Shear Bracing |
|
Re-inspection required |
9/15/26: see previous notes regarding drywall spacing from floor to bottom plate. I noted several sections of drywall upstairs that are spaced between 1" to 2". Make corrections and reschedule when ready. |
| 09/17/2026 |
COT - RSBU - Interior Shear Bracing |
|
Passed |
9-17-26. All corrections have been made OK to proceed |