Inspection History Details
Inspection Status: Re-inspection required
Inspection History: BULD - Electrical Clearance
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2026 | BULD - Electrical Clearance | Re-inspection required | 7/6/26: gas piping overhead must be properly secured throughout, Pex not pressurized, DWV NOT UNDER TEST, STOPPED INSPECTION house is not ready for intermediate inspection. | |
| 07/07/2026 | BULD - Electrical Clearance | Re-inspection required | 7/7/26: leak at garage from above ceiling. Items listed above not addressed, flex duct req to have supports 4' o.c throughout, tear at flex duct in kitchen area and laundry room and upstairs, remove felt paper from support at 2nd floor,seal all penetrations through top plate throughout, mechanical chase must be properly sealed, properly support exhaust duct throughout, properly install return flex at plenum box upstairs, top plates that are bored 50% or greater require FHA plate with 8 nails both sides, Boca plates required throughout, properly support exhaust duct to exhaust fan with proper strap (tape will not work). ELECTRICAL HAS NOT BEEN WALKED, PLEASE WALK HOME BEFORE RECALLING INSPECTION. STOPPED INSPECTION. RE-INSPECTION FEE | |
| 07/10/2026 | BULD - Electrical Clearance | Re-inspection required | 07/10/2026 Missing riser and metal address tag, label temp power breaker. |