Parcel: 141461840


Addresses:

9551 E WYNALDA DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0225-00092

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
10/08/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10-8-25: add anchor bolts to marked locations, add shot pins on non bearing walls at 32" o.c. And 24" o.c. For interior load bearing walls-shot pins are required within 6" at the end/both sides of sill plates, add nails 8" o.c. At joints to garage shear wall. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE ADDED.
10/09/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready Add A35 and H25 clip at back patio East end. Add shot pins and anchor bolt at marked areas. Add king stud at primary shower window. Add bracing to truss A1E. Add 2 nails every 24” at ledger in bedroom 3. Add shims and H25 clips at truss A3 bearing points. (At entry) 10/9/2025
10/10/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 10.10.25
corrections made