Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0225-00091
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 5-20-25, masa clips not nailed throughout, over penetrated nails along shear walll sheathing on west side-nails shall not over penetrated more than 1/16". Nail all nails at garage shear wall flush. Missing shot pins throughout-shot pin required within 6" of end of each plate and a minimum of 2 are required per plate. Clarification needed on RSP4 spacing-the east side has them installed every other stud while the west side has them installed every other 3rd stud. Missing 3x3 washer plate at SW11. Anchor bolts for SW11 are required at 23" o.c. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED. | |
| COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 5-29-25: missing nut on anchor bolt at garage entry and plans call for HUC26-2 hangers at garage. | ||
| 05/30/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Canceled | 5-30-25, canceled by contractor. | |
| 05/30/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 5-30-25, exterior clips/sheathing approved. |