Parcel: 141461870


Addresses:

9585 E WYNALDA DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Roof Nailing 

Permit Number - TC-MDP-0225-00091

Inspection Description - COT - RSBU - Roof Nailing 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
05/20/2025 COT - RSBU - Roof Nailing  Re-inspection required 5-20-25, masa clips not nailed throughout, over penetrated nails along shear walll sheathing on west side-nails shall not over penetrated more than 1/16". Nail all nails at garage shear wall flush. Missing shot pins throughout-shot pin required within 6" of end of each plate and a minimum of 2 are required per plate. Clarification needed on RSP4 spacing-the east side has them installed every other stud while the west side has them installed every other 3rd stud. Missing 3x3 washer plate at SW11. Anchor bolts for SW11 are required at 23" o.c. STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED.
COT - RSBU - Roof Nailing  Re-inspection required 5-29-25, roof has already been loaded, therefore, provide a letter to the city for review/approval indicating that roof nailing was done per approved plans and meets standards set forth by the 2018 IRC.
05/30/2025 COT - RSBU - Roof Nailing  Passed 5-30-25, roof nailing approved.