Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-0224-00256
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2024 | COT - RSEL - Electrical Final | Re-inspection required | 8/22/24: panel schedule not complete, condensate drains not properly installed must have 90 degree and terminate 6" above grade, seal all penetrations through stucco, properly install gasket at water heater vent, cut gray water to grade, A/C condenser being over amped, Post-tension tag missing at hose bib, cut clean out to grade, cover plates missing on exterior, no plans on site, provide proper ladder for attic access, engineering final not passed. | |
08/23/2024 | COT - RSEL - Electrical Final | Re-inspection required | 8/22/24: panel schedule not complete, condensate drains not properly installed must have 90 degree and terminate 6" above grade, seal all penetrations through stucco, properly install gasket at water heater vent, cut gray water to grade, A/C condenser being over amped, Post-tension tag missing at hose bib, cut clean out to grade, cover plates missing on exterior, no plans on site, provide proper ladder for attic access, engineering final not passed. 8/23/24: A/C unit being over amped all other issues addressed. |
|
08/26/2024 | COT - RSEL - Electrical Final | Passed | Corrections were made. 8/26/2024 |