Inspection Status: Canceled

Inspection History: COT - RSPL - Gas Pressure Test 

Permit Number - TC-MDP-0224-00251

Inspection Description - COT - RSPL - Gas Pressure Test 

Inspection Status - Canceled

Date Description Inspector Results Comments
10/01/2024 COT - RSPL - Gas Pressure Test  Canceled Canceled per contractor. 10/1/2024
10/02/2024 COT - RSPL - Gas Pressure Test  Re-inspection required Canceled per contractor. 10/1/2024
10/2/24: Receptacle at hallway missing, circuits tied in together plans call for 23 circuits only 17 circuits visible at panel. Electrical wiring must be per plans, 12" of clearance required between pex and can lights, gauge for gas piping pressure test is damaged, all penetrations through vapor barrier must be sealed, all wiring must be secured 12" from box. WR receptacle required for electrical clearance. DWV not under test.
10/24/2024 COT - RSPL - Gas Pressure Test  Passed 10-24-24 Gas pressure test approved.