Inspection History Details
Inspection Status: Canceled
Inspection History: BULD - Electrical Clearance
Permit Number - TC-MDP-0224-00251
Inspection Description - BULD - Electrical Clearance
Inspection Status - Canceled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2024 | BULD - Electrical Clearance | Canceled | Canceled per contractor. 10/1/2024 | |
10/02/2024 | BULD - Electrical Clearance | Re-inspection required | Canceled per contractor. 10/1/2024 10/2/24: Receptacle at hallway missing, circuits tied in together plans call for 23 circuits only 17 circuits visible at panel. Electrical wiring must be per plans, 12" of clearance required between pex and can lights, gauge for gas piping pressure test is damaged, all penetrations through vapor barrier must be sealed, all wiring must be secured 12" from box. WR receptacle required for electrical clearance. DWV not under test. |
|
10/10/2024 | BULD - Electrical Clearance | Passed | 10/10/24: ECO TEP clearance |