Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - BULD - SWG Clearance
Permit Number - TC-MDP-0224-00251
Inspection Description - COT - BULD - SWG Clearance
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2024 | COT - BULD - SWG Clearance | Re-inspection required | Canceled per contractor. 10/1/2024 10/2/24: Receptacle at hallway missing, circuits tied in together plans call for 23 circuits only 17 circuits visible at panel. Electrical wiring must be per plans, 12" of clearance required between pex and can lights, gauge for gas piping pressure test is damaged, all penetrations through vapor barrier must be sealed, all wiring must be secured 12" from box. WR receptacle required for electrical clearance. DWV not under test. 10/10/24: Test gauge at gas piping must be 15psi gauge and be tested to 15psi, 12" clearance required from pex to can light, seal sleeves for underground plumbing and electrical, provide updated electrical drawings, support gas piping midway at vertical runs. |